Features
- AC outdoor power system for different environments
- Double wall construction
- Special treatment and paint technology (against corrosion)
- Different thermal management options
- Integrated Delta UPS J serie 2,2 kVA
- Battery compartment with battery shelf (up to 100 Ah)
- Space for telecom or datacom equipment 19''/5U
- Protection against vandalism
- Integrated lightning protection
- Dimensions (HxWxD) 1493 x 752 x 947 mm
Design The outdoor AC power system OAPS J2.2-230 MPS is especially designed for wireless base stations. Double wall, aluminum panel cabinet provides significant protection against solar radiation. The standard cabinet is equipped with one front door. Three points locking mechanism with patented lock is vandal resistant. The battery compartment with battery shelves is located in the bottom. Upper part is reserved for the electronic equipment. All inside equipments is fixed to 4 vertical cabinet supporters. It allows easy system configuration.
Cable management The cabinets are equipped with cable inlets from bottom (via plinth) and from the top (top part of rear side). The left and right side of the cabinet could be easily opened to ensure easy access to input / output cable management.
Thermal management Delta outdoors could be supplied with different cooling systems. Standard systems are equipped with the simplest and the most efficient solution with fans (roof) and air filters (door). The heat exchangers (air to air) with capacity 50 - 150 W/K could be installed on the door in more advanced application. For the most demanding environments, the air conditioners (up to 2000W) are available. The climate environment inside outdoor could be controlled by intelligent climate controller CCM 1.
Power system The standard system contains Delta J series UPS 2.2 KVA which cooperate with external battery up to 100Ah. Additional space 19' / 5U could be used for the user equipment. A large number of different options provide solutions for global applications in different environments.
|
Input |
|
|
|
Input voltage range Input current, nominal
|
| 160 ... 275 Vrms 8,5 A
|
|
|
Output |
|
|
|
Output voltage, nominal Output power, nominal Efficiency
|
| 230 Vrms (single phase) 2,2 kVA; 1,6 kW @ P.F.=0,73 # 87%
|
|
|
AC / DC distribution |
|
|
|
Battery fuses Load fuses
Cooling unit
|
| 2 x MCB 63A 3 x MCB (16, 6, 6A) RCD 25 A / 30mA MCB 2A
|
|
|
Environment |
|
|
|
Operating temperature
|
| -33 ... + 40 °C (ETS 300 019-1-4 kl. 4.1)
|
|
|