Features
- Outdoor power system for different environments
- Double wall construction
- Special treatment and paint technology
- Different thermal management options
- Modular power system up to 14,4kW with DPR 1200B-48 rectifiers
- Integrated battery & thermal management
- Separate battery compartment
- Space for telecom or datacom equipment 19''
- Protection against vandalism
- Integrated lightning protection
- Dimensions (HxWxD) 1911 x 770 x 770 mm
Design The outdoor DC power system ODPS 1200B-48-12 MPS is especially designed for wireless base stations. Double wall, aluminum sheet cabinet provides significant protection against solar radiation and noise reduction.
The standard cabinet is equipped with one front door. Three points locking mechanism with patented lock is vandal resistant. The battery compartment with battery shelves is located in the bottom. Upper part is reserved for the electronic equipment. Delta ETS standard allows easy system configuration.
Cable management The cabinets are equipped with cable inlets from bottom (via plinth) and from top (rear part of the roof). The left and / or right side of the cabinet and the roof could be easily removed to ensure easy access to input / output cable management.
Thermal management Delta outdoors could be supplied with different cooling systems. Standard systems are equipped with the simplest and the most efficient solution with fans (roof) and air filters (door). The heat exchangers (air to air) with capacity 50 - 150 W/K could be installed on the door in more advanced application. For the most demanding environments, the air conditioners (up to 2000W) are available. The climate environment inside outdoor could be controlled by intelligent climate controller CCM 1.
Power system The integrated, high power density, DC modular power system allows flexible adaptations. It is the key factor for the success of this power system and it offers cost-effective and reliable solutions for global applications in different environments.
|
Input |
|
|
|
Input voltage range
|
| 184 .. 276 Vrms
|
|
|
Output |
|
|
|
Output voltage, nominal Output power, maximum Output current, nominal Efficiency
|
| 53,5 VDC 12 x 1200 W 269 ADC @ 14,4 kW; 53,5 V 91%
|
|
|
Distribution |
|
|
|
DC distribution Battery fuses Critical load fuses
No of critical load fuses
LVDs
|
| Configurable Max 6 x NH00 Max 2xMCB (80-120A), 16 x MCB (do 63A) Max 1xNH00, 3xMCB (80-120A), 6xMCB (do 63A) Battery LVD No critical loads PLD
|
|
|
Environment |
|
|
|
Operating temperature
|
| -33 ... + 40 °C
|
|
|
System |
|
|
|
Rectifier Power system controller
|
| DPR 1200B-48 PSC 1000 (PSC 1 or PSC 3 as an option)
|
|
|